Blue outdoor cable for electronic control equipment is a cable normally used for signal transmission, even weak signals, as it is shielded.
Strengths:
Shielded with Al/Pet tape
Non-fire propagating
Low halogen emission and UV resistant
CEI UNEL 36762
Also ideal for use with gland chains
USE: Used in electronic control equipment, signal detection in outdoor intrusion detection systems, where increased protection against weathering and in particular ultraviolet rays is required.
INSTALLATION: For fixed installation indoors and outdoors. Can be installed on catwalks, pipes, conduits and similar systems. Can be laid together with energy cables having both 450/750 V and 0.6/1 kV markings used for systems with rated voltage to earth (Uo) up to 400 V.
Layout layers (starting from the inside):
Conductor
Insulator
Separator
Drainage
Shear wire
Shielding
Sheath
Package contains: 1 x BLUE electronic control equipment cable FOR OUTDOOR 6x0.22 - per meter
Conductors: annealed red copper - CEI EN 60228 (Table 9)
Insulation: PVC of R2 quality - CEI EN 50363
Core colors: alarm colors - red and black (power supply)
Separator: pet tape
Drainage: annealed red copper
Shielding: Al/Pet tape
Sheath cutting wire: Pet
Sheath: PVC quality RZ - CEI EN 50363
Sheath color: blue RAL 5015 with red RAL 3000 stripe
Not fire-propagating: CEI 20-22/II
Non-flame propagating: CEI EN 60332-1-2
Low halogen emission: (< 22 %) - CEI EN 50267-2-1 - IEC 60754-1
Resistant to oil: CEI 20-34/0-1
UV resistant: HD 605
Electrical resistance: CEI EN 60228
Test voltage: 2000 V
Maximum operating temperature: 70 °C
Short-circuit temperature: 160 °C
Min. laying temperature: 0 °C
Bending radius: Ø x 8
Marking: BERICA CAVI S.P.A. ITALY ALA CEI UNEL 36762 C-4 (Uo=400 V) Formation O.R. UV RESISTANT CEI 20-22 II CE Year/Batch
For other information please contact us.
The item you will receive may differ in some features from the one depicted in the photo, depending on the production batch. Despite this, the functionality is maintained.