USE
Suitable for the transmission of signals and commands for the interconnection of instrumentation and control systems with digital or analog signal transmission in outdoor environments, where increased protection against weather and particularly ultraviolet rays is required.
LAYING
For fixed and mobile indoor and outdoor installation. Can be installed on catwalks, pipes, conduits and similar systems. Possibility of laying together with energy cables having both 450/750V and 0.6/1 kV markings used for systems with rated voltage to earth (Uo) up to 400 V.
CHARACTERISTICS
Conductors: annealed red copper cl.5 / CEI EN 60228 (Table 9)
Insulation: PVC quality R2 / CEI EN 50363
Core colors: (UNEL 00722 x 2/3x1.5 mm2)/ DIN 47100
Sheath: PVC of Rz quality / CEI EN 50363
Sheath color: blue RAL 5015 with red RAL 3000 stripe
Not fire-propagating: CEI 20-22/II
Non-flame propagating: CEI EN 60332-1-2
Low halogen emission: (< 22 %) / CEI EN 50267-2-1 - IEC 60754-1
Resistant to oil: CEI 20-34/0-1
UV resistant: HD 605
Electrical resistance: relative to section / CEI EN 60228 (Table 9)
Test voltage: 2000 V
Maximum operating temperature: 70°C
Short-circuit temperature: 160°C
Min laying temperature: 0°C
Bending radius: Ø x 6
Maximum standard twisting (2x cable): 10 turns/meter
Marking: BERICA CAVI S.P.A. ITALY FROR CEI UNEL 36762 C-4 (Uo=400 V) CEI 20-22 II O.R. UV RESISTANT CE Year/Lot - Training - 00000 m
Package contains: 1 x FROR CABLE 0.6/1kV BLUE x EXTERNAL 4X1 - per meter
For more information please contact us. The item you receive may differ in some features from the one depicted in the photo, depending on the production batch. Despite this, functionality is maintained.